Circuit Breaker Sizing
Size a circuit breaker for a load per NEC 240.4. Continuous loads are sized at 125% per NEC 210.20.
Steady-state load in amperes
General purpose breaker
Breaker sized at 100% of load
Breaker Size20A
Next standard size above load
Minimum Wire Gauge
14 AWG
NEC Table 310.16 (copper, 75 deg C)
Reference: NEC 240.4 (overcurrent protection) • NEC 210.20 (continuous loads at 125%) • NEC 210.12 (AFCI) • NEC 210.8 (GFCI)